Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Raven Meadows Golf Resort: Difference between revisions

From FireAlarmPedia
mNo edit summary
Line 7: Line 7:
| FACP: Edwards 6616 (Inoperable)<br /> FACP Location: Entrance Hallway <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Continuous <br />Date of last known Upgrade: 1989 <br />Year Opened: 1978 <br /> Year Decommissioned: 2021
| FACP: Edwards 6616 (Inoperable)<br /> FACP Location: Entrance Hallway <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Continuous <br />Date of last known Upgrade: 1989 <br />Year Opened: 1978 <br /> Year Decommissioned: 2021
|}
|}
'''Raven Meadows Golf Resort''' is a golf course located in Alder Flats, AB at 454065 Highway 22. Its amenities include a campground an 18-hole golf course, and formerly a hotel with a restaurant and pro shop. This page will cover the former hotel. The resort was opened in 1978, and the hotel underwent a system upgrade in 1989 confirmed by the heat detectors' labels. As of August 2021, the system was not inspected in 15 years, the panel had failed, and as a result, the system was inoperable. The system was last serviced in 2006.
'''Raven Meadows Golf Resort''' is a golf course located in at 454065 Highway 22, Alder Flats, AB. Its amenities include a campground an 18-hole golf course, and formerly a hotel with a restaurant and pro shop. This page will cover the former hotel. The resort was opened in 1978, and the hotel underwent a system upgrade in 1989 confirmed by the heat detectors' labels. As of August 2021, the system was not inspected in 15 years, the panel had failed, and as a result, the system was inoperable. The system was last serviced in 2006.


In October 2021, the hotel burnt down to the ground.
In October 2021, the hotel burnt down to the ground.

Revision as of 13:06, 16 April 2024

System Specifications
FACP: Edwards 6616 (Inoperable)
FACP Location: Entrance Hallway
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Date of last known Upgrade: 1989
Year Opened: 1978
Year Decommissioned: 2021

Raven Meadows Golf Resort is a golf course located in at 454065 Highway 22, Alder Flats, AB. Its amenities include a campground an 18-hole golf course, and formerly a hotel with a restaurant and pro shop. This page will cover the former hotel. The resort was opened in 1978, and the hotel underwent a system upgrade in 1989 confirmed by the heat detectors' labels. As of August 2021, the system was not inspected in 15 years, the panel had failed, and as a result, the system was inoperable. The system was last serviced in 2006.

In October 2021, the hotel burnt down to the ground.

System Specifications (1989-2021)

FACP

The hotel was protected by an Edwards 6616 conventional fire alarm system. The panel was located in the entrance hallway. The system had three zones in use, and the system coding was continuous.

As of August 2021, the panel suffered a main board failure, and was in stuck in alarm for all three zones plus an spare zone. Therefore, the system was no longer functional.

Notification Appliances

All notification appliances except one were Edwards 439D-10AWC vibrating bells (10” gong). The one in the lobby was vandalized; both labels ripped off, and the gong was mounted on the striker with a crosshead screw instead of the original hex bolt.

In the hallway to the restaurant, there was an Edwards “Durabel” 6100D vibrating bell (10" gong). It was painted over, except for the label.

All bells were installed in 1989.

Initiating Devices

Pull Stations

All pull stations except for one were Edwards 275-C111 conventional pull stations. These were located at every exit, including an awkward install by a sliding glass door pointed toward the door handle; this was because there is no room for the pull station to be mounted on the wall, as it would be blocked by curtains.

There was one original Edwards 270-SPO in the restaurant hallway exit.

Automatic Detection Devices

There were Edwards 281C rate of rise/fixed-temperature heat detectors throughout the hotel. They were not replaced despite the recall due to the company being out of business by the time. There was no sprinkler system.