Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Hotel Le Germain Calgary: Difference between revisions

From FireAlarmPedia
mNo edit summary
(All accurate now. HOLY FUCK THIS IS THE WORST SYSTEM EVER)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Edwards EST3 <br /> FACP Location: Unknown <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: 20BPM (First Stage) <br> Temporal (GA) <br> Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: N/A <br />Year Opened: 2010
| FACP: Edwards EST3 <br /> FACP Location: Main Floor Office CACF (Main Node)<br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: 20BPM 1kHz (First Stage) <br> Temporal 1kHz (GA) <br> Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2010s<br />Year Opened: 2009
|}
|}
'''Hotel Le Germain Calgary''' is a large upscale hotel located at 899 Centre Street South, in Downtown Calgary, Alberta, Canada. The hotel is known for its spa, and has a restaurant and bar on site. The hotel has a 4 star rating, and is very highly reviewed. The hotel opened in 2010, and the fire alarm system is original.
'''Hotel Le Germain Calgary''' is a large upscale hotel located at 899 Centre Street South, in Downtown Calgary, Alberta, Canada. The hotel is known for its spa, and has a restaurant and bar on site. The hotel has a 4 star rating, and is very highly reviewed. The building was built in 2009, and the hotel opened in 2010; the fire alarm system is original.
 
The building is also connected to an office tower and Le Germain Residences (108 9 Ave SW). The fire alarm system monitors both of these buildings.  
==System Specifications (2009-present)==
==System Specifications (2009-present)==
====FACP====
====FACP====
The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs Edwards’ Signature-series addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The first stage signal is a 20BPM tone, followed by a temporal tone in general alarm. It is unknown if there are voice messages for either stage.
The buildings are protected by an Edwards EST3 addressable fire alarm system. The system is a network with 7 nodes, see list below. The system runs Edwards’ Signature-series addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The first stage signal is a 20BPM tone, followed by a temporal tone in general alarm. No messages are played.
 
Panels are in the following locations:
 
* Main Floor Office CACF (Main Node)
* Office Floor 9
* Parkade P0 Electrical Room
* Hotel Main Floor CACF
* Hotel 10th Floor Electrical Room
* Condo 18th Floor Electrical Room
 
===== Annunciators =====
There are Edwards EST 3-LCDANN LCD annunciators with LCDXL1 displays in the main floor office CACF, and behind the hotel front desk.  
 
====Notification Appliances====
====Notification Appliances====
=====Common Areas=====
=====Common Areas & Offices=====
All notification appliances are Edwards 965-7A-8RW speaker/strobes (white, ceiling-mount, 8” round, 15/75cd, 70V).
All notification appliances are Edwards 965-3A-8RW speaker/strobes (white, ceiling-mount, 8” round, 30cd, 70V).
 
There is an EST "Genesis" G4R-S7VM speaker/strobe (red, wall-mount, no marking, set to 15cd) in one renovated office unit.
 
There is also an EST "Genesis" G1R-VM remote strobe (red, wall-mount, no marking, set to 15cd) in the 2nd floor office area.
=====Guest Rooms=====
=====Guest Rooms=====
All guest rooms have Edwards 965-1A-4RW remote speakers (white, ceiling-mount, 4” round, 70V) mounted near the doorway.
All guest rooms have Edwards 965-1A-4RW remote speakers (white, ceiling-mount, 4” round, 70V) mounted near the doorway.
Line 20: Line 39:
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the common areas of the hotel, mounted on EST SIGA-SB bases.
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the buildings.
[[]
 
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the restaurant kitchen and garbage chute.
 
All detectors are mounted on SIGA-SB bases.  
 
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on the air handling units.
 
==== Modules ====
There are EST SIGA-CT1 addressable monitor modules and EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches and kitchen suppression system.
 
There are EST SIGA-CR addressable relays for dampers, door holders, and fans.
 
There are EST SIGA-IM isolator modules on the SLCs.

Revision as of 23:06, 26 April 2024

System Specifications
FACP: Edwards EST3
FACP Location: Main Floor Office CACF (Main Node)
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM 1kHz (First Stage)
Temporal 1kHz (GA)
Strobes Synchronized: Yes, EST
Date of last known Upgrade: 2010s
Year Opened: 2009

Hotel Le Germain Calgary is a large upscale hotel located at 899 Centre Street South, in Downtown Calgary, Alberta, Canada. The hotel is known for its spa, and has a restaurant and bar on site. The hotel has a 4 star rating, and is very highly reviewed. The building was built in 2009, and the hotel opened in 2010; the fire alarm system is original.

The building is also connected to an office tower and Le Germain Residences (108 9 Ave SW). The fire alarm system monitors both of these buildings.

System Specifications (2009-present)

FACP

The buildings are protected by an Edwards EST3 addressable fire alarm system. The system is a network with 7 nodes, see list below. The system runs Edwards’ Signature-series addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The first stage signal is a 20BPM tone, followed by a temporal tone in general alarm. No messages are played.

Panels are in the following locations:

  • Main Floor Office CACF (Main Node)
  • Office Floor 9
  • Parkade P0 Electrical Room
  • Hotel Main Floor CACF
  • Hotel 10th Floor Electrical Room
  • Condo 18th Floor Electrical Room
Annunciators

There are Edwards EST 3-LCDANN LCD annunciators with LCDXL1 displays in the main floor office CACF, and behind the hotel front desk.

Notification Appliances

Common Areas & Offices

All notification appliances are Edwards 965-3A-8RW speaker/strobes (white, ceiling-mount, 8” round, 30cd, 70V).

There is an EST "Genesis" G4R-S7VM speaker/strobe (red, wall-mount, no marking, set to 15cd) in one renovated office unit.

There is also an EST "Genesis" G1R-VM remote strobe (red, wall-mount, no marking, set to 15cd) in the 2nd floor office area.

Guest Rooms

All guest rooms have Edwards 965-1A-4RW remote speakers (white, ceiling-mount, 4” round, 70V) mounted near the doorway.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the buildings.

There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the restaurant kitchen and garbage chute.

All detectors are mounted on SIGA-SB bases.

There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on the air handling units.

Modules

There are EST SIGA-CT1 addressable monitor modules and EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches and kitchen suppression system.

There are EST SIGA-CR addressable relays for dampers, door holders, and fans.

There are EST SIGA-IM isolator modules on the SLCs.