Line 17: | Line 17: | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are System Sensor 1400A conventional ionization smoke detectors throughout the hotel's common areas. The building is equipped with a wet sprinkler system; the tamper and flow switches have dedicated zones on the panel. | There are System Sensor 1400A conventional ionization smoke detectors throughout the hotel's common areas. The building is equipped with a wet sprinkler system; the tamper and flow switches have dedicated zones on the panel. | ||
[[Category:Alberta]] | |||
[[Category:Hotels]] |
Revision as of 18:10, 23 May 2024
System Specifications |
---|
FACP: Mirtone 7532 FACP Location: Main Entrance Vestibule System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Same NAC Only Date of last known Upgrade: N/A Year Opened: 1997 |
Best Western is a hotel chain headquartered in Phoenix, Arizona, USA. They have locations worldwide under several brands. This particular hotel is located at 4520 40 ST, Olds, Alberta, Canada. The hotel opened in 1997, and was renovated in 2017. The fire alarm system is original. This page will also cover the attached Boston Pizza restaurant, which shares a fire alarm system with the hotel.
System Specifications (1997-present)
FACP
The building is protected by a Mirtone 7532 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is likely temporal.
Notification Appliances
All notification appliances are Edwards "Integrity" 757-5A-T horn/strobes (red, wall-mount, 15cd) or Mirtone INT-5A-T horn/strobes (red, wall-mount, 15cd). These are located throughout the common areas and in all guest rooms.
Pull Stations
All pull stations are Edwards 270-SPO conventional single-action pull stations.
Automatic Detection Devices
There are System Sensor 1400A conventional ionization smoke detectors throughout the hotel's common areas. The building is equipped with a wet sprinkler system; the tamper and flow switches have dedicated zones on the panel.