More actions
No edit summary |
|||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Edwards EST3 | | FACP: Edwards EST3 <br>FACP Location: Behind Front Desk<br />System Type:Addressable (Two-stage) <br /> System Line Voltage: 120VAC<br />NAC Voltage:70.7VRMS (audible) <br> 24VDC (visual) <br>System Coding: Unknown <br>Strobes Synchronized: Yes, EST<br />Date of last known Upgrade: 2013 <br />Year Opened: 1956 | ||
FACP Location: Behind Front Desk<br />System Type:Addressable (Two-stage) <br /> System Line Voltage: 120VAC<br />NAC Voltage:70.7VRMS (audible) <br> 24VDC (visual) | |||
System Coding: Unknown | |||
Strobes Synchronized: Yes, EST<br />Date of last known Upgrade: 2013 <br />Year Opened: 1956 | |||
|} | |} | ||
'''Cambridge Red Deer Hotel & Conference Centre''' is a hotel in Red Deer, Alberta. It has a large conference centre, as well as a pool, and many other amenities. It opened in 1956, and was renovated in 2007. The fire alarm system was upgraded in 2013. This page will cover both the current and previous fire alarm systems. | '''Cambridge Red Deer Hotel & Conference Centre''' is a hotel in Red Deer, Alberta. It has a large conference centre, as well as a pool, and many other amenities. It opened in 1956, and was renovated in 2007. The fire alarm system was upgraded in 2013. This page will cover both the current and previous fire alarm systems. | ||
Line 48: | Line 43: | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
Unknown. | Unknown. | ||
[[Category:Alberta]] | |||
[[Category:Hotels]] |
Revision as of 18:53, 23 May 2024
System Specifications |
---|
FACP: Edwards EST3 FACP Location: Behind Front Desk System Type:Addressable (Two-stage) System Line Voltage: 120VAC NAC Voltage:70.7VRMS (audible) 24VDC (visual) System Coding: Unknown Strobes Synchronized: Yes, EST Date of last known Upgrade: 2013 Year Opened: 1956 |
Cambridge Red Deer Hotel & Conference Centre is a hotel in Red Deer, Alberta. It has a large conference centre, as well as a pool, and many other amenities. It opened in 1956, and was renovated in 2007. The fire alarm system was upgraded in 2013. This page will cover both the current and previous fire alarm systems.
System Specifications (2013-present)
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located behind the front desk. The system runs EST’s Signature addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the messages and/or tones are unknown at this time.
Notification Appliances
The notification appliances vary throughout the hotel. The hallways, lobby area, conference centre, and most other common areas have EST 757-5A-SS70 “Enhanced Integrity” speaker/strobes (70V, red, wall-mount). The pool area has System Sensor “SpectrAlert Advance” SPRKA speakers (70V, red, wall-mount) with EST CS405-7A-T weatherproof remote strobes (red, wall-mount, 15/75cd) beside or underneath them.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the facility. The detectors in the rooms are mounted on EST SIGA-AB4G sounder bases, and are mounted on EST SIGA-SB bases in common areas. There is also a sprinkler system with waterflow detection.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
System Specifications (Previous System) (Early 1990s-2013)
System Specifications |
---|
FACP: Edwards EST3 System Type: Conventional System Line Voltage: 120VAC NAC Voltage:24VDC System Coding: Continuous Strobes Synchronized: Yes, EST |
FACP
The building was protected by an Edwards EST3 conventional fire alarm system. The panel was located behind the front desk. The system coding was continuous.
Notification Appliances
Most areas of the hotel had Edwards 439D-6AWC vibrating bells (6” gong) on EST "Integrity" 403-5A-R strobe plates (15cd). The conference centre had Edwards 439D-10AWC vibrating bells (10” gong), also on 403-5A-R strobe plates (15cd). There were also Mircom FHS-240R horn/strobes (red, wall-mount, 15cd) in the lobby.
Initiating Devices
Pull Stations
The pull stations were a mix of Edwards 275-C111 conventional single-action pull stations and Mirtone 73303 conventional single-action pull stations.
Automatic Detection Devices
Unknown.