| FACP: EST QuickStart QS4 <br />FACP Location: Main Entrance Vestibule <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: N/A <br />Year Opened: 2005 | | FACP: EST QuickStart QS4 <br />FACP Location: Main Entrance Vestibule <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: N/A <br />Year Opened: 2005 | ||
|} | |} | ||
'''Deerfoot Inn & Casino''' is a casino hotel located at #1000 11500 35 St SE, Calgary, AB. It was built in 2005, and the fire alarm system is original. | '''Deerfoot Inn & Casino''' is a casino hotel located at #1000 11500 35 St SE, Calgary, AB. It was built in 2005, and the fire alarm system is original. | ||
== System Specifications (2005-present) == | == System Specifications (2005-present) == | ||
==== FACP ==== | ==== FACP ==== | ||
The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST’s Signature addressable protocol, and the system coding is temporal. | The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST’s Signature addressable protocol, and the system coding is temporal. | ||
===== Booster Panels ===== | ===== Booster Panels ===== | ||
There is likely an Edwards BPS6A 6 amp power supply. | There is likely an Edwards BPS6A 6 amp power supply. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All notification appliances are EST “Genesis” G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd). <br> There are no notification appliances in the guest rooms. | All notification appliances are EST “Genesis” G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd). <br> There are no notification appliances in the guest rooms. | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations are EST SIGA-270 addressable pull stations. | All pull stations are EST SIGA-270 addressable pull stations. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are EST SIGA-PS addressable photoelectric smoke detectors for elevator recalls, mounted on SIGA-SB bases. The rest of the hotel is protected by a sprinkler system. | There are EST SIGA-PS addressable photoelectric smoke detectors for elevator recalls, mounted on SIGA-SB bases. The rest of the hotel is protected by a sprinkler system. | ||
==== Modules ==== | ==== Modules ==== | ||
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
[[Category:Calgary]] | |||
[[Category:Hotels]] | |||
[[Category:Casinos]] |
Revision as of 14:50, 25 May 2024
System Specifications |
---|
FACP: EST QuickStart QS4 FACP Location: Main Entrance Vestibule System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Year Opened: 2005 |
Deerfoot Inn & Casino is a casino hotel located at #1000 11500 35 St SE, Calgary, AB. It was built in 2005, and the fire alarm system is original.
System Specifications (2005-present)
FACP
The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST’s Signature addressable protocol, and the system coding is temporal.
Booster Panels
There is likely an Edwards BPS6A 6 amp power supply.
Notification Appliances
All notification appliances are EST “Genesis” G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd).
There are no notification appliances in the guest rooms.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors for elevator recalls, mounted on SIGA-SB bases. The rest of the hotel is protected by a sprinkler system.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.