==== FACP ==== | ==== FACP ==== | ||
The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the basement telecom room. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert signal is 20BPM, followed by the temporal alarm signal. | The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the basement telecom room. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert signal is 20BPM, followed by the temporal alarm signal. | ||
===== Annunciators ===== | |||
There are a total of 8 EST QSA-2-S annunciators on the system, located at each nurse's station, in most stairwells, and in the main entrance vestibule. | |||
===== Booster Panels ===== | ===== Booster Panels ===== | ||
There are three Edwards BPS10A 10 amp booster power supplies next to the panel. | There are three Edwards BPS10A 10 amp booster power supplies next to the panel. | ||
Line 22: | Line 26: | ||
==== Modules ==== | ==== Modules ==== | ||
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
==== EOLs ==== | ==== EOLs ==== | ||
There are Edwards EOL-P1 end of line resistor plates on all signaling and sprinkler circuits. | There are Edwards EOL-P1 end of line resistor plates on all signaling and sprinkler circuits. | ||
[[Category:Calgary]] | [[Category:Calgary]] | ||
[[Category:Healthcare]] | [[Category:Healthcare]] |
Revision as of 14:37, 26 May 2024
System Specifications |
---|
FACP: EST QuickStart QS4 FACP Location: Basement Telecom Room System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: 20BPM (alert) Temporal (alarm) Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Year Opened: 2004 |
Newport Harbour Care Centre is a long-term care facility or nursing home located at 10 Country Village Cove NE, Calgary, AB. It was built in 2004, and has the original fire alarm system.
System Specifications (2004-present)
FACP
The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel is located in the basement telecom room. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert signal is 20BPM, followed by the temporal alarm signal.
Annunciators
There are a total of 8 EST QSA-2-S annunciators on the system, located at each nurse's station, in most stairwells, and in the main entrance vestibule.
Booster Panels
There are three Edwards BPS10A 10 amp booster power supplies next to the panel.
Notification Appliances
All notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building.
There are EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in the crawlspaces and staff rooms.
All EST detectors are mounted on SIGA-SB bases.
The kitchens have FDD CF-135 135 degree fixed-temperature heat detectors, wired to EST SIGA-CT1 addressable monitor modules.
There are EST SIGA-DH duct detector housings with SIGA-PS addressable photoelectric smoke detector heads on all air handling units.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all signaling and sprinkler circuits.