North Hill Centre: Difference between revisions

From FireAlarmPedia
No edit summary
No edit summary
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Notifier NFS2-640C
| FACP: Notifier NFS2-640C <br>FACP Location: Food Court Entrance<br />System Type: Addressable (Networked) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br>System Coding: 20BPM (Alert) <br>Temporal (Alarm)<br />Date of last known Upgrade: 2018-19 <br />Year Opened: 1958, 1973, 2000
FACP Location: Food Court Entrance<br />System Type: Addressable (Networked) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC  
 
System Coding: 20BPM (Alert)
 
Temporal (Alarm)<br />Date of last known Upgrade: 2018-19 <br />Year Opened: 1958, 1973, 2000
|}
|}
'''North Hill Centre''' was the first shopping mall in Calgary, Alberta. It is located off at 1632 14 Ave NW, Calgary. The mall spans two floors, with professional offices (dental, pediatric and doctor clinics) on the second level. The mall was built in 1958, expanded in 1973, and then majorly renovated in 2000. The fire alarm system is from the 2000 renovation.
'''North Hill Centre''' was the first shopping mall in Calgary, Alberta. It is located off at 1632 14 Ave NW, Calgary. The mall spans two floors, with professional offices (dental, pediatric and doctor clinics) on the second level. The mall was built in 1958, expanded in 1973, and then majorly renovated in 2000. The fire alarm system is from the 2000 renovation.

Revision as of 16:17, 26 May 2024

System Specifications
FACP: Notifier NFS2-640C
FACP Location: Food Court Entrance
System Type: Addressable (Networked)
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Date of last known Upgrade: 2018-19
Year Opened: 1958, 1973, 2000

North Hill Centre was the first shopping mall in Calgary, Alberta. It is located off at 1632 14 Ave NW, Calgary. The mall spans two floors, with professional offices (dental, pediatric and doctor clinics) on the second level. The mall was built in 1958, expanded in 1973, and then majorly renovated in 2000. The fire alarm system is from the 2000 renovation.

System Specifications (2000-present)

FACP

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located at the food court entrance. The system runs Notifier's CLIP addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal in alarm signal.

Notification Appliances

The notification appliances are mainly System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd) horn/strobes.

Dollarama opened 2019, and has System Sensor "L-Series" PC2RLA horn/strobes (red, ceiling-mount, bilingual marking, set to 30cd).

Winners opened 2018, and has System Sensor "SpectrAlert Advance" PC2WA (white, ceiling-mount, set to 15cd) horn/strobes.

Initiating Devices

Pull Stations

All pull stations are Notifier NFM-950KB conventional single-action two-stage pull stations. These are attached to Notifier MMX-101A addressable modules.

Automatic Detection Devices

There are System Sensor CPX-551 addressable ionization smoke detectors throughout the mall, mounted on System Sensor BX501A bases.

There is a Notifier FSP-851A addressable photoelectric smoke detector on the second floor, mounted on a System Sensor B210LPA base as a deficiency replacement.