| FACP: EST iO500 <br />FACP Location: Main Mechanical Room <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR (Panel NACs) <br>24VDC (Booster NACs) <br />System Coding: Temporal <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: N/A <br />Year Opened: 2013 | | FACP: EST iO500 <br />FACP Location: Main Mechanical Room <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR (Panel NACs) <br>24VDC (Booster NACs) <br />System Coding: Temporal <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: N/A <br />Year Opened: 2013 | ||
|} | |} | ||
'''Shepard Landfill''' is a waste management facility owned and operated by the City of Calgary. The facility is located at 12111 68 Street SE, in Calgary, Alberta, Canada. This page will cover Building D, which is a vehicle storage garage. The building was built in 2013, and the fire alarm system is original. | |||
'''Shepard Landfill''' is a waste management facility owned and operated by the City of Calgary. | |||
==System Specifications== | ==System Specifications== | ||
====FACP==== | ====FACP==== | ||
The building is protected by an EST iO500 addressable fire alarm system. | The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main mechanical room. The system runs EST’s Signature addressable protocol, and the system coding is temporal. | ||
=====Boosters===== | =====Boosters===== | ||
There are eight EST BPS10A booster power supplies; 4 of which are located in the main mechanical room, and 4 are located in the main electrical room. | There are eight EST BPS10A booster power supplies; 4 of which are located in the main mechanical room, and 4 are located in the main electrical room. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
=====Vehicle Bays===== | =====Vehicle Bays===== | ||
All audible notification appliances are Edwards “AdaptaHorn” 889D-AW explosion-proof remote horns (red, wall-mount). | All audible notification appliances are Edwards “AdaptaHorn” 889D-AW explosion-proof remote horns (red, wall-mount). <br>All visual notification appliances are Edwards 116DEGEX-FJ explosion-proof remote strobes (125cd) | ||
=====Mechanical Rooms===== | =====Mechanical Rooms===== | ||
All notification appliances are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd). | All notification appliances are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd). | ||
=====Wash Bay===== | =====Wash Bay===== | ||
All notification appliances are Edwards “Integrity” 757-7A-T horn/strobes (red, wall-mount, 15/75cd). | All notification appliances are Edwards “Integrity” 757-7A-T horn/strobes (red, wall-mount, 15/75cd). | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations in the vehicle bays are Edwards MPSR1-S45W conventional explosion-proof single-action pull stations. | All pull stations in the vehicle bays are Edwards MPSR1-S45W conventional explosion-proof single-action pull stations. These are wired to EST SIGA-CT1 addressable monitor modules. <br>All other areas have EST SIGA-270 addressable single-action pull stations. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in all mechanical rooms, mounted on EST SIGA-SB bases. | There are EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in all mechanical rooms, mounted on EST SIGA-SB bases. | ||
====Modules==== | ====Modules==== | ||
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br> There are also EST SIGA-IM addressable isolator modules on each SLC loop. | There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br> There are also EST SIGA-IM addressable isolator modules on each SLC loop. | ||
[[Category:Calgary]] |
Revision as of 15:11, 27 May 2024
System Specifications |
---|
FACP: EST iO500 FACP Location: Main Mechanical Room System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR (Panel NACs) 24VDC (Booster NACs) System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: N/A Year Opened: 2013 |
Shepard Landfill is a waste management facility owned and operated by the City of Calgary. The facility is located at 12111 68 Street SE, in Calgary, Alberta, Canada. This page will cover Building D, which is a vehicle storage garage. The building was built in 2013, and the fire alarm system is original.
System Specifications
FACP
The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main mechanical room. The system runs EST’s Signature addressable protocol, and the system coding is temporal.
Boosters
There are eight EST BPS10A booster power supplies; 4 of which are located in the main mechanical room, and 4 are located in the main electrical room.
Notification Appliances
Vehicle Bays
All audible notification appliances are Edwards “AdaptaHorn” 889D-AW explosion-proof remote horns (red, wall-mount).
All visual notification appliances are Edwards 116DEGEX-FJ explosion-proof remote strobes (125cd)
Mechanical Rooms
All notification appliances are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Wash Bay
All notification appliances are Edwards “Integrity” 757-7A-T horn/strobes (red, wall-mount, 15/75cd).
Initiating Devices
Pull Stations
All pull stations in the vehicle bays are Edwards MPSR1-S45W conventional explosion-proof single-action pull stations. These are wired to EST SIGA-CT1 addressable monitor modules.
All other areas have EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in all mechanical rooms, mounted on EST SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are also EST SIGA-IM addressable isolator modules on each SLC loop.