More actions
mNo edit summary |
No edit summary |
||
Line 18: | Line 18: | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Siemens HFP-11 addressable multisensor smoke/heat detectors throughout the building. There is also a sprinkler system with waterflow detection. | There are Siemens HFP-11 addressable multisensor smoke/heat detectors throughout the building. There is also a sprinkler system with waterflow detection. | ||
==== Modules ==== | ==== Modules ==== | ||
There are Siemens XTRI-M addressable monitor modules supervising the sprinkler system's tamper and flow switches. | There are Siemens XTRI-M addressable monitor modules supervising the sprinkler system's tamper and flow switches. | ||
[[Category:Facilities]] | [[Category:Facilities]] | ||
[[Category:Office Buildings]] | [[Category:Office Buildings]] | ||
[[Category:Calgary]] |
Revision as of 09:50, 28 May 2024
System Specifications |
---|
FACP: Siemens FireFinder XLS FACP Location: CACF Room System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: 20BPM +Message(Alert) Temporal +Message (Alarm) Strobes Synchronized: Yes, Siemens Date of last known Upgrade: 2011 Year Opened: 1983 |
Western Canadian Place is an office tower complex located at 801 6 Street Southwest, in Downtown Calgary, Alberta, Canada. The building consists of two towers: the south tower, which is 31 floors, and the north tower, which is 41 floors. The building opened in 1983, and the fire alarm system was upgraded in 2011. No information is known about the fire alarm system prior to 2011.
System Specifications (2011-present)
FACP
The building is protected by a Siemens FireFinder XLS addressable fire alarm system. The system is a network of over 20 panels, and the main node is located in the CACF room. The system runs Siemens’ FirePrint addressable protocol, and has voice evacuation capabilities. The system is configured for zoned two-stage operation. When a device is activated, the floor of the alarm as well as the floors above and below the alarm will sound the alert signal at 20BPM. If that floor goes into the alarm signal, which is a temporal signal followed by a message, all other floors will play the alert signal
Notification Appliances
Most notification appliances are Siemens SE-MC-CW-B speaker/strobes (white, ceiling-mount, set to 15cd, bilingual lettering). Some areas have Siemens SEC-W remote speakers (white, ceiling-mount) for additional sound coverage.
Initiating Devices
Pull Stations
All pull stations are Siemens HMS-2S addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Siemens HFP-11 addressable multisensor smoke/heat detectors throughout the building. There is also a sprinkler system with waterflow detection.
Modules
There are Siemens XTRI-M addressable monitor modules supervising the sprinkler system's tamper and flow switches.