System Specifications |
---|
FACP: Notifier AFP-200 FACP Location: Main Entrance Vestibule System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) Temporal (Alarm) Strobes Synchronized: Yes, Partial Self-Sync Date of last known Upgrade: 2000s Year Opened: 2000 |
Nickle House is an adult continuing care facility operated under the Carewest marque of Alberta Health Services, the local health authority in Alberta, Canada. This particular location is located at 950 Robert Road NE in Calgary, AB. It was built in 2000, and the system is original to the building.
System Specifications
FACP
The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel is located in the front entrance vestibule. The system runs Notifier's CLIP addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal.
Annunciators
There is a Notifier LCD-80 annunciator in the nurses office.
Notification Appliances
Most notification appliances are System Sensor "SpectrAlert" P2415WA horn/strobes (white, wall-mount, 15cd/electromechanical).
There are a few System Sensor "SpectrAlert Advance" P4RA horn/strobes (red, wall-mount, set to 15cd) as deficiency replacements.
Initiating Devices
Pull Stations
All pull stations are Notifier MPS-950KB two stage pull stations, wired to two Notifier MMX-101A addressable monitor modules each.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA bases.
Waterflow Switches
There is one Potter PS10 waterflow pressure switch attached to a dry system, wired to a Notifier MMX-101A addressable monitor module.
EOLs
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.