System Specifications
FACP: EST QuickStart QS4
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, Self-Sync
Date of last known Upgrade: N/A
Year Opened: 2011

Cochrane Community Health Centre is a medical centre located at 60 Grande Boulevard, in Cochrane, Alberta, Canada. The building opened in 2011, and the fire alarm system is original.

System Specifications

FACP

The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel location is unknown. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal.

Annunciators

There is an EST QSA-2-S annunciator in the main entrance vestibule.

Notification Appliances

All notification appliances are EST “Genesis” G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd). The horn and strobe are coded separately by an EST G1M “Signal Master” module.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

None noticed.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are EST SIGA-CR addressable relay modules serving various purposes.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.