Holiday Inn Express & Suites Edmonton North

From FireAlarmPedia
Revision as of 10:58, 30 September 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS2-640C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2007

Holiday Inn Express is a chain of hotels owned by IHG. The chain is headquartered in Denham, England. This particular hotel is located at 13742 50 Street Northwest, in Edmonton, Alberta, Canada. The hotel opened in 2007, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Annunciators

There is a Notifier ACM-24AT annunciator next to the main FACP, likely installed for code compliance.

Notification Appliances

Common Areas

All notification appliances are System Sensor “SpectrAlert” P2415A horn/strobes (red, wall-mount, 15cd, set to electromechanical).

Guest Rooms

Each guest room has a System Sensor “SpectrAlert” S2415WA remote strobe (white, wall-mount, 15cd) paired with a System Sensor PA400SWA silenceable mini-horn (white, wall-mount).

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices

There are smoke detectors present, however the models are unknown at this time.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Notifier FRM-1A addressable relay modules serving various purposes.

There are Notifier ISO-XA isolator modules on all SLCs.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and Class-B signal circuits.