Denny's (Red Deer)

From FireAlarmPedia
Revision as of 15:47, 24 August 2025 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST1-2Z3
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Strobes Synchronized: Yes, Self-sync
Date of last known Upgrade: N/A
Most Recent Known Modification: 2020 (Heat Detectors)
Year Opened: 2001

Denny’s is a diner-style restaurant chain. This particular restaurant is located at 2940 Gaetz Ave, Red Deer, Alberta. The restaurant opened in 2001, and the fire alarm system is original.

System Specifications (2001-present)

FACP

The building is protected by an Edwards EST1-2Z3 conventional fire alarm system. The panel is located in the main entrance vestibule.

Notification Appliances

All notification appliances are Edwards 439D-6AWC vibrating bells (6" gong) mounted on Edwards 403-5A-R strobe plates (15cd).

Initiating Devices

Pull Stations

All pull stations are Edwards 270-SPO conventional single-action pull stations.

Automatic Detection Devices

There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors in each washroom.
The kitchen suppression system is tied into the fire alarm.

EOLs

There are Edwards EOL-P1 end-of-line resistor plates on all circuits.