System Specifications |
---|
FACP: Edwards FireShield Plus System Line Voltage: 120VAC NAC Voltage: 24VFWR Date of last known Upgrade: 2012 Year Opened: 1962 |
Webster Niblock School is an elementary school in Medicine Hat, AB. It was opened on September 3, 1962, however only the pull stations are original to the building. It has undergone 2 major additions since construction. One in 1994, and 3 portable units were attached in 2007. However upon examination of Satellite imagery these appear to have been detached. A small addition was constructed in an unknown location in 1988.
System Specifications
FACP
The fire alarm panel is an Edwards "FireShield Plus" FSP-1004 (grey cabinet) installed in 2012 that replaced an Edwards 2280 installed during the 1988 addition. It likely replaced some sort of Edwards 120VAC panel from 1962. The new FireShield does continuous despite having coding options obviously due to the self coded Genesis horn strobes installed in the portables. This may have changed since the removal of the portables sometime after 2016.
Notification Appliances
The notification appliances are Edwards 439D-6AWC vibrating bells that were installed during the 1988 addition. The original horns were still installed as of 2013 and were surprisingly not Edwards but Federal Signal "Vibratone" 350 120VAC mechanical horns. However these horns no longer operate. In the now removed 2008 portable addition were EST "Genesis" G1R-HDVM (red, wall mount, no fire marking) horn/strobes.
Initiating Devices
Pull Stations
The pull stations were Edwards 270-SPO pull stations. Most of them are the original first generation 270-SPO (FIRE ALARM, classic shield), however the additions have the newer (1990s-2000s generation) Edwards 270-SPO.
Automatic Detection Devices
Heat Detectors
There is one Edwards CF135-2 fixed/ROR heat detector in the Kitchen located in the 1994 addition.
Duct Detectors
There is one visible Edwards SD-2W 2-wire conventional photoelectric duct detector installed on an air handling unit in the Gymnasium Equipment Room. It is unknown when this was installed, as it was installed when the 2280 was around.