System Specifications |
---|
FACP: EST QuickStart QS4 FACP Location: Unknown System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: 20BPM (First Stage) Temporal (GA) Strobes Synchronized: Yes, Self-Sync Date of last known Upgrade: N/A Year Opened: 2011 |
Cochrane Community Health Centre is a medical centre located at 60 Grande Boulevard, in Cochrane, Alberta, Canada. The building opened in 2011, and the fire alarm system is original.
System Specifications
FACP
The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel location is unknown. The system runs EST’s Signature-series addressable protocol, and is configured for two-stage operation. First stage coding is 20BPM, followed by temporal in general alarm. The general alarm timer length is five minutes.
Annunciators
There is an EST QSA-2-S annunciator in the main entrance vestibule, equipped with a QS4-CPU-1 control card and two SL30 zone annunciation modules.
Notification Appliances
All notification appliances are EST “Genesis” G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd). The horn and strobe are coded separately by an EST G1M “Signal Master” module.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
None noticed, waterflow present.
Modules
There is likely an EST SIGA-CT2 dual-input monitor module supervising the sprinkler system’s tamper and flow switches. [[Category:Facilitie]