System Specifications |
---|
FACP: Notifier NFS2-640C FACP Location: Lobby System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Wheelock Only Date of last known Upgrade: 2021 Year Opened: 1996 |
Canmore Inn & Suites is a 3-star hotel located at 1402 Bow Valley Trail, Canmore, AB. It was built in 1996 as Ramada, and became Canmore Inn & Suites in 2017. The fire alarm system was upgraded in 2021, only the pull stations are original.
System Specifications (2021 present)
FACP
The building is protected by a Notifier NFS2-640C conventional fire alarm system. The panel is located in the lobby, and has an NCA-2 display. The system coding is temporal.
Notification Appliances
All common area notification appliances are System Sensor "L-Series" HRLA horns (red, wall-mount) horns on Wheelock RSSP-24MCW strobe plates (red, set to 15cd).
The guest rooms contain EST 964-3A-103 mini-horn/strobes (white, 30cd), these remained from the previous system.
Initiating Devices
Pull Stations
All pull stations are Edwards 270-SPO conventional pull stations. These were kept from the original system.
Automatic Detection Devices
All smoke detecors are System Sensor "i3" C2W-BA photoelectric smoke detectors, which also remained. There is also a sprinkler system with waterflow detection.
Former System Specifications (1996-2021)
System Specifications |
---|
FACP: Simplex 4100U FACP Location: Lobby System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous? Strobes Synchronized: No |
FACP
The hotel was protected by a Simplex 4100U conventional fire alarm system. The panel was located in the lobby, and had a 3 bay cabinet; it replaced the original EST ESA2000 around 2005. The system coding was likely continuous.
Notification Appliances
All common area notification appliances were Edwards 439D-6AWC vibrating bells (6" gong) on EST "Integrity" 403-5A-R strobe plates (red, 15cd).
The workout room had the aforementioned bell installed remotely.
The pool area had an Edwards 439D-10AWC vibrating bell (10" gong) on an EST 403-5A-R strobe plate, due to higher ambient noise levels.
The guest rooms contained EST 692-3A-103 mini-horn/strobes (white, 30cd), these are still in service.
Initiating Devices
Pull Stations
All pull stations were Edwards 270-SPO conventional pull stations; these remain on the current system.
Automatic Detection Devices
All smoke detectors are System Sensor C2W-BA photoelectric smoke detectors, these are still installed.