Hotel Le Germain Calgary

From FireAlarmPedia
Revision as of 23:06, 26 April 2024 by Alberta Fire Alarms (talk | contribs) (All accurate now. HOLY FUCK THIS IS THE WORST SYSTEM EVER)
System Specifications
FACP: Edwards EST3
FACP Location: Main Floor Office CACF (Main Node)
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM 1kHz (First Stage)
Temporal 1kHz (GA)
Strobes Synchronized: Yes, EST
Date of last known Upgrade: 2010s
Year Opened: 2009

Hotel Le Germain Calgary is a large upscale hotel located at 899 Centre Street South, in Downtown Calgary, Alberta, Canada. The hotel is known for its spa, and has a restaurant and bar on site. The hotel has a 4 star rating, and is very highly reviewed. The building was built in 2009, and the hotel opened in 2010; the fire alarm system is original.

The building is also connected to an office tower and Le Germain Residences (108 9 Ave SW). The fire alarm system monitors both of these buildings.

System Specifications (2009-present)

FACP

The buildings are protected by an Edwards EST3 addressable fire alarm system. The system is a network with 7 nodes, see list below. The system runs Edwards’ Signature-series addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The first stage signal is a 20BPM tone, followed by a temporal tone in general alarm. No messages are played.

Panels are in the following locations:

  • Main Floor Office CACF (Main Node)
  • Office Floor 9
  • Parkade P0 Electrical Room
  • Hotel Main Floor CACF
  • Hotel 10th Floor Electrical Room
  • Condo 18th Floor Electrical Room
Annunciators

There are Edwards EST 3-LCDANN LCD annunciators with LCDXL1 displays in the main floor office CACF, and behind the hotel front desk.

Notification Appliances

Common Areas & Offices

All notification appliances are Edwards 965-3A-8RW speaker/strobes (white, ceiling-mount, 8” round, 30cd, 70V).

There is an EST "Genesis" G4R-S7VM speaker/strobe (red, wall-mount, no marking, set to 15cd) in one renovated office unit.

There is also an EST "Genesis" G1R-VM remote strobe (red, wall-mount, no marking, set to 15cd) in the 2nd floor office area.

Guest Rooms

All guest rooms have Edwards 965-1A-4RW remote speakers (white, ceiling-mount, 4” round, 70V) mounted near the doorway.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the buildings.

There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the restaurant kitchen and garbage chute.

All detectors are mounted on SIGA-SB bases.

There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on the air handling units.

Modules

There are EST SIGA-CT1 addressable monitor modules and EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches and kitchen suppression system.

There are EST SIGA-CR addressable relays for dampers, door holders, and fans.

There are EST SIGA-IM isolator modules on the SLCs.