System Specifications |
---|
FACP: EST QuickStart QS1 FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Genesis Self-Sync Date of last known Upgrade: N/A Year Opened: 2002 |
450 Midpark Way SE is the address of a disused fire station in Calgary, Alberta, Canada. The building used to be Calgary Fire Department Station 26, and was closed when the Midnapore Multi-Services Centre opened. The building was built in 2002 and the fire alarm system is original.
System Specifications (2000s-present)
FACP
The building is protected by an EST QuickStart QS1 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST’s Signature addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Initiating Devices
Pull Stations
There are no pull stations in this building.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors in the office hallways on both floors, mounted on EST SIGA-SB bases.