Cervus Equipment John Deere Calgary

From FireAlarmPedia
Revision as of 16:30, 23 September 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2012

Cervus Equipment is an equipment dealer that serves Canada. This particular location specifically sells John Deere stuff, like tractors and attachments. Despite the location being called Calgary, it is located at 292177 Crosspointe Road, Rocky View, AB, near Balzac. It was built in 2012, and has the original system.

System Specifications (2012-present)

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located to the left of the main entrance. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are from System Sensor's "SpectrAlert Advance" line of products. The indoor notification appliances are System Sensor P2RA horn/strobes (red, wall-mount, set to 15cd).

For outdoor notification, there are System Sensor SRKA weatherproof remote strobes (red, wall-mount) around the exterior of the building.

Initiating Devices

Pull Stations

All pull stations are Notifier N-MPS-SA addressable single action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors in some areas, mounted on System Sensor B210LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.