Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

East Edmonton Health Centre

From FireAlarmPedia
Revision as of 20:32, 25 September 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: EST QuickStart QS4
FACP Location: Unknown
System Type: Two-Stage ddressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2009

East Edmonton Health Centre is a community health centre and urgent care clinic located at 7910 112 Ave NW, Edmonton, AB. It is owned and operated by Alberta Health Services. The building was built in 2009, and opened in 2010. The fire alarm system is original.
The building is annexed to the closed Cromdale School, which opened in 1930 and closed in 1980. It is unknown if the systems are connected.

System Specifications

FACP

The building is protected by an EST QuickStart QS4 addressable fire alarm system. The panel location is unknown. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal for the alarm signal.

Annunciators

There is an EST QSA-2-S annunciator with a QS4-CPU-2 CPU in the main entrance vestibule.

Notification Appliances

All notification appliances are EST “Genesis” G1-HDVM horn/strobes (white, wall-mount, no marking, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building.
Certain areas have EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.