Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Farm Boy (Trainyards)

From FireAlarmPedia
Revision as of 19:01, 26 September 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards iO1000
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2021

Farm Boy is a Canadian chain of grocery stores owned by Sobeys/Empire. They have locations across Ontario, and are headquartered in Ottawa. This particular store is located at 830 Belfast Road, in the Trainyards area of Ottawa, Ontario, Canada. The store was built in 2021, and the fire alarm system is original.

System Specifications

FACP

The building is protected by an Edwards iO1000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.

Notification Appliances

Most notification appliances are Edwards “Genesis” G1-HDVM horn/strobes (white, wall-mount, no marking, set to 15cd).

Some areas have Edwards GC-HDVM horn/strobes (white, ceiling-mount, no marking, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGC-270B addressable bilingual single-action pull stations.

Automatic Detection Devices

None noticed.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are EST SIGA-CR addressable relay modules serving various purposes.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.