System Specifications
FACP: Notifier NFS-320C
FACP Location: Front Desk
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2008

Hampton Inn & Suites is a hotel chain owned by Hilton. The chain is headquartered in Mclean, Virginia, USA, and has locations globally. This particular hotel is located at 18304 100 Ave NW, in Edmonton, Alberta, Canada. The hotel was built in 2008, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located behind the front desk. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All common area notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
Each guest room has a System Sensor PA400SWA silenceable mini-horn (white) and a System Sensor SWA remote strobe (white, wall-mount, set to 15cd). The horns are mounted above the strobes.

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout all common areas, mounted on System Sensor B710LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.