Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

IKEA (Calgary)

From FireAlarmPedia
Revision as of 11:31, 30 September 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: Unknown
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage:70.7VRMS (audible)
24VDC (visual)
System Coding: 20BPM + Message (Alert)
Temporal + Message (Alarm)
Date of last known Upgrade: 2018
Year Opened: 2004

IKEA is a large multinational chain of stores primarily selling ready-to-assemble furniture. This particular store is located at 8000 11 Street Southeast, in Calgary, Alberta, Canada. The store opened in 2004, and the fire alarm system is mostly original, with unknown upgrades completed in 2018.

System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel is likely located in an electrical room. The system runs Edwards' Signature addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The evacuation tones are believed to be a 20BPM tone plus an alert message for the alert signal, followed by a temporal tone with a custom evacuation message as the alarm signal. The message scripts are unknown, and the general alarm timer length is five minutes.

Annunciators

There is an Edwards EST3-6ANN annunciator in the main entrance vestibule.

Notification Appliances

All areas except washrooms have Edwards "Genesis" G4R-S7V15 speaker/strobes (red, wall-mount, no lettering, 70V, 15cd). The public washrooms have Edwards 965-7A-8SW speaker/strobes (white, ceiling-mount, 70V, 15/75cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on EST SIGA-SB bases. There is also a sprinkler system with waterflow detection.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.

EOLs