System Specifications |
---|
FACP: Simplex 4007ES FACP Location: Kitchen System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: 2015 Year Opened: 1984 |
McDonald's is the world's second largest fast food chain. This particular restaurant is located at 63 Crowfoot Way NW, in Calgary, Alberta, Canada. The restaurant was built in 1984, and was renovated in 2015. The fire alarm system was partially upgraded during the 2015 renovation.
System Specifications
FACP
The building is protected by a Simplex 4007ES conventional fire alarm system. The panel is located in the kitchen. The system coding is temporal.
Notification Appliances
Most notification appliances are Simplex "TrueAlert" 4906-9127 horn/strobes (red, wall-mount, set to 15cd).
The customer washrooms have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
Most pull stations are Edwards 270-SPO conventional single-action pull stations.
There is a Tyco-Grinnell MS-401GR conventional single-action pull station at the main entrance as a deficiency replacement.
Automatic Detection Devices
There are Simplex "TrueAlarm" 4098-9601 conventional photoelectric smoke detectors in all public areas of the restaurant.
There are Potter CR-135W conventional 135°F fixed-temperature/rate-of-rise heat detectors in the kitchen.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all circuits.