Mount Royal University Main Building

From FireAlarmPedia
Revision as of 19:22, 13 October 2024 by TwentyThree33 (talk | contribs) (Hron/strobe. Also my fucking computer decided to switch to the Canadian multilingual standard keyboard randomly, so it replaced the slash with é)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: Various
System Type: Two-Stage Networked Addressable
System Line Voltage: 120VAC
NAC Voltage: 70VRMS (speakers)
24VDC (horn/strobes)
System Coding: 20BPM 1kHz (alert)
Temporal (horn/strobes, alarm)
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2000s
Year Opened: 1972

Mount Royal University is a medium-sized university located at 4825 Mount Royal Gate SW, Calgary, Alberta. This page will cover the main building, located on the Lincoln Park Campus. It was built in 1972, and the fire alarm system was upgraded in the 2000s.

System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panels are located in the main CACF room on the second floor, and are part of a campus-wide network. The system runs EST’s Signature addressable protocol, and is equipped with voice-evacuation. The system is also configured for two-stage operation. The alert signal is a 20BPM 1kHz tone on the speakers followed by a custom message, and the alarm signal activates the horn/strobes, self-coded to temporal.

Accessories

There is an EST “FireWorks” graphic computer in the CACF room.

Notification Appliances

There are EST “Genesis” GC-S7VM speaker/strobes (white, ceiling-mount, no marking, set to 15cd) throughout. These play the alert signal.
The notification appliances used for the evacuation signal are EST G1R-HOV15 horn/strobes (red, wall-mount, no marking, 15cd). Some of these are mounted on Notifier MPS-BB backboxes. One is installed upside-down.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage pull stations.

Automatic Detection Devices

None noticed.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

There are EST SIGA-CR addressable relay modules serving various purposes.

EOLs

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.