System Specifications |
---|
FACP: EST iO64 FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2016 Year Opened: 1990 |
Prairie Winds Spray Park is an outdoor spray park owned by the City of Calgary. The park is located at 223 Castleridge Boulevard Northeast, in Calgary, Alberta, Canada. This page covers the locker room/mechanical building, which was built in 1990 and completely renovated in 2016. The fire alarm system was upgraded as part of the 2016 renovation.
System Specifications (2016-present)
FACP
The building is protected by an EST iO64 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST’s Signature addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA2-HRS addressable fixed/rate-of-rise heat detectors in all mechanical and janitorial rooms, mounted on EST SIGA-SB bases. The building is equipped with a wet sprinkler system with waterflow detection.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.