System Specifications |
---|
FACP: Mircom FX-2000 FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: 2014 Year Opened: 2004 |
The Reader Rock Garden Residence is a historic house located at 3025 Spiller Road SE, in Calgary, Alberta, Canada. The house is an exact replica of the original residence, and was built in 2004. The house is currently home to the Reader Rock Garden Cafe. The fire alarm system was upgraded in 2014.
System Specifications (2014-present)
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located at the main entrance. The system runs Mircom’s CLIP addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are Mircom “Select-A-Horn/Strobe” FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).
Initiating Devices
Pull Stations
All pull stations are Mircom MS-401AD addressable single-action pull stations.
Automatic Detection Devices
There are Mircom MIX-2251APA addressable photoelectric smoke detectors in some areas and at the top of each stairwell.
All storage rooms have Mircom MIX-5251RAPA addressable 135°F fixed-temperature/rate-of-rise heat detectors.
The main electrical room has a Mircom MIX-5251APA addressable 135°F fixed-temperature heat detector.
All detectors are mounted on System Sensor B210LPA bases.
Modules
There are Mircom MIX-M500MAPA addressable monitor modules supervising the kitchen suppression system.
EOLs
There are Mircom MP-300 end-of-line resistor plates on all sprinkler and signal circuits.