SAIT/AUArts/Jubilee Station

From FireAlarmPedia
Revision as of 22:27, 11 October 2024 by Alberta Fire Alarms (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Simplex 4007ES
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: SmartSync
Date of last known Upgrade: 2018
Year Opened: 1987

SAIT/AUArts/Jubilee Station is a Red Line LRT station in Calgary, Alberta. This station serves the Southern Alberta Institute of Technology, Alberta University of the Arts, and the Southern Alberta Jubilee Auditorium. The station opened in 1987, and was renovated in 2018. The renovated station received many upgrades, including a new fire alarm system.

System Specifications

FACP

The station is protected by a Simplex 4007ES addressable fire alarm system. The panel location is unknown, but is based on the size and age of the system. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, multi-candela).

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9004 addressable LED single-action pull stations.

Automatic Detection Devices

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the station. They are mounted on 4098-9792 bases.

EOLs

There are Simplex 2081-9040C end-of-line resistor plates on all signal circuits.