More actions
System Specifications |
---|
FACP: Edwards EST3X FACP Location: Main Lobby by Escalators System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) Temporal (Alarm) Strobes Synchronized: Yes Date of last known Upgrade: 2017 Year Opened: 2001 |
Scotiabank Theatre is a theatre chain owned by Cineplex. This particular theatre is located at 6455 Macleod Trail Southwest, in Calgary, Alberta, Canada. The theatre is attached to CF Chinook Centre, however the fire alarm systems are not connected. The theatre opened in 2001, following the large expansion and renovation of the mall. The fire alarm system is original with the exception of the FACP and smoke detectors.
System Specifications
FACP
The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main lobby, to the left of the escalators. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal in for the alarm coding. This panel replaced an Edwards EST3, of which the cabinet remains, and is used as a junction box.
Annunciators
There is an Edwards EST3-LCDANN annunciator near the west entrance.
Notification Appliances
All notification appliances are Edwards 439D-10AWC vibrating bells (10” gong) on EST 403-5A-R strobe plates (15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Edwards SIGA-PD addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches. There are also EST SIGA-CR addressable relays serving various purposes.
EOLs
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.