System Specifications
FACP: Simplex 4007ES
FACP Location: Data Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: 2019
Year Opened: 1980

TAS Refrigerated Distribution Inc. is a cold storage facility located at 4060 78 Avenue Southeast, in Calgary, Alberta, Canada. The building opened in 1980, and the fire alarm system was upgraded in 2019.

System Specifications (2019-present)

FACP

The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located in the main data room. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Annunciators

There is a Simplex 4606-9202 annunciator in the main entrance vestibule.

Notification Appliances

The cold-storage areas have System Sensor “SpectrAlert Advance” P2RKA weatherproof horn/strobes (red, wall-mount, set to 15cd).

All other areas have System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to 15cd).

For outdoor notification, there is a System Sensor “SpectrAlert Advance” SRKA weatherproof remote strobe (red, wall-mount) outside the main entrance.

Initiating Devices

Pull Stations

Most pull stations are Simplex 4099-9004 addressable single-action pull stations. The freezers have Simplex 2099-9754 conventional single-action pull stations, wired to Simplex 4090-9001 addressable monitor modules.

Automatic Detection Devices

There is a Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detector in the second floor electrical room, mounted on a Simplex 4098-9792 addressable base. The building is equipped with a sprinkler system, and there are three Notifier NFS-320C pre-action systems in the building.

Modules

There are Simplex 4090-9001 addressable monitor modules and Simplex 4090-9002 addressable relay modules serving various purposes in the building.

EOLs

There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler and signal circuits.