System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2011 Year Opened: 1974 |
The Thornhill Tri-Service Building is a multi-tenant building owned by the City of Calgary. The building is located at 6617 Centre Street Northwest, in Calgary, Alberta, Canada, and consists of the Thornhill Community Health Centre, Thornhill Child Care Centre, and the Thornhill branch of the Calgary Public Library. The building was built in 1974, and the fire alarm system was fully upgraded in 2011.
System Specifications (2011-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are System Sensor “SpectrAlert Advance” P2CWA horn/strobes (white, ceiling-mount, set to 15cd).
For exterior notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount, set to 75cd).
Initiating Devices
Pull Stations
All pull stations are Notifier N-MPS-SA addressable single-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the daycare and library.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in most closets and mechanical rooms in all units
The air handling units have Notifier DNRA duct detector housings with Notifier FSP-851A addressable photoelectric smoke detector heads.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all signal circuits.