System Specifications |
---|
FACP: Simplex 4100U FACP Location: Main Entrance (Node 1) System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2011 Year Opened: 1931 |
The Calgary Public Building is a historic office building located at 205 8 Avenue SE, in Calgary, Alberta, Canada. The building is owned and operated by the City of Calgary. The building was built in 1931, and renovated in 2011. The fire alarm system was upgraded as part of the 2011 renovation.
System Specifications (2011-present)
FACP
The building is protected by a Simplex 4100U addressable fire alarm system. There are 3 nodes on the system: Node 1 is located at the main entrance, Node 2 is in the 3rd floor electrical room, and Node 3 is in the 7th floor electrical room. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal. Synchronization is provided by System Sensor MDLA sync modules at each node.
Notification Appliances
Most notification appliances are System Sensor “SpectrAlert Advance” PC2WA horn/strobes (white, ceiling-mount, set to 15cd).
Some areas have System Sensor P2WA horn/strobes (white, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
Most pull stations are Simplex 4099-9001 addressable single-action pull stations.
Some areas have Simplex 4099-9004 addressable single-action pull stations as deficiency replacements.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in all mechanical and electrical rooms, and in the elevator lobbies and stairwells, mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
EOLs
There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.