System Specifications |
---|
FACP: Edwards EST3 FACP Location: Various System Type: Two-Stage Networked Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) Temporal (Alarm) Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2023 Year Opened: 1976 |
Kingsway Mall is a shopping mall located at 1 Kingsway NW, in Edmonton, Alberta, Canada. The mall is anchored by Walmart and Hudsons Bay. The mall was built in 1976, and was renovated in 2009. The fire alarm system was upgraded as part of the 2009 renovation.
System Specifications (2009-present)
Note: This system supervises all areas of the mall except Hudsons Bay. To see details for that system, click here.
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. This is a networked system with many nodes; one node is located in the Walmart entrance vestibule. The system runs Edwards’ Signature addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal.
Annunciators
There is an Edwards EST3-LCDANN annunciator with an LCDXL1 display mounted on a pedestal in the food court entrance vestibule.
Notification Appliances
Main Mall & Tenants
Most areas have Edwards “Genesis” G1-HDVM horn/strobes (white, wall-mount, no marking, set to 15cd).
Some areas, including some tenants and washrooms, have Edwards GC-HDVM horn/strobes (white, ceiling-mount, no marking, set to 15cd).
Some washrooms have Edwards GCF-HDVM horn/strobes (white, ceiling-mount, FIRE marking, set to 15cd).
Some newer tenants have Edwards GCAVWN horn/strobes (white, ceiling-mount, no marking, set to 15cd).
Bath & Body Works has Edwards GCVWN remote strobes (white, ceiling-mount, no marking, set to 15cd).
Walmart
All notification appliances are a mix of Edwards “Genesis” G1AVWN horn/strobes (white, wall-mount, no marking, set to 15cd) and Edwards G1VWN remote strobes (white, wall-mount, no marking, set to 15cd).
These are mounted on pillars throughout the store, with 2 horn/strobes and 2 remote strobes, with horn/strobes on 2 opposite sides and remote strobes on the other 2 opposite sides.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the lower floor, mounted on EST SIGA-SB bases with SIGA-TS4 trim skirts.
Some areas tenants have Edwards SIGA-OSD addressable optical smoke detectors, these can also be found as deficiency replacements.
There are Edwards SIGA-HRD addressable thermal heat detectors by each escalator.
Some other areas have Edwards SIGA-PD addressable photoelectric smoke detectors.
The food court CRU’s have Edwards SIGA-COD addressable carbon monoxide detectors.
All above detectors are mounted on Edwards SIGA-SB bases.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.
There are Edwards “SignalMaster” G1M-RM signal control modules on all NACs to allow 4-wire operation for two-stage.
EOLs