System Specifications |
---|
FACP: Simplex 4100ES FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 70VRMS (audible) System Coding: 24VDC (visual) Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: 2013 Year Opened: 2005 |
Health Sciences/Jubilee Station is a light rail station located by the Walter C. Mackenzie Health Sciences Centre in Edmonton, AB. It serves both Metro and Capital Lines. The station was originally built in 2005, and had an expansion in 2013 to add a pedway system. There are two fire alarm systems, which were installed in 2013 and 2016 respectively.
System Specifications (Pedway & Majority) (2013-present)
FACP
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel location is unknown. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice-evacuation. The tones and/or messages are unknown at this time.
Notification Appliances
All notification appliances are Simplex “TrueAlert” 4906-9154 speaker/strobes (white, ceiling-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout, mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs
There are Simplex 2081-9040C end-of-line resistors on the signal and sprinkler circuits.
System Specifications (Additional Coverage) (2016-present)
System Specifications |
---|
FACP: Simplex 4007ES FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC VoltageL 24VDC System Coding: Temporal Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: 2016 Year Opened: 2013 |
FACP
The building is protected by a Simplex 4007ES addressable fire alarm system. The panel location is unknown. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
Annunciators
There is a Simplex 4606-9605 LCD annunciator paired with a 4602-9101 LED annunciator in the lobby.
Notification Appliances
The only notification appliance is a Simplex “TrueAlert” 4906-9128 horn/strobe (red, ceiling-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex 4098-9714 addressable photoelectric smoke detectors mounted on Simplex 4098-9792 bases.
EOLs
There are Simplex 2081-9040C end-of-line resistors on the signal circuit.