Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Boardwalk Retirement Community

From FireAlarmPedia
Revision as of 15:43, 8 September 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier AFP-200
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: N/A
Date of last known Upgrade: 1998
Year Opened: 1970

Boardwalk Retirement Community is a seniors only apartment building located at 3520 31 Street NW, in Calgary, Alberta, Canada. The building was built in 1970, and the fire alarm system was upgraded in 1998.

System Specifications (1998-present)

FACP

The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s CLIP addressable protocol, and the system coding is temporal.

Notification Appliances

Most notification appliances are Mircom BL-10B motor bells (10” gong).
The following bells are installed on the system, in order of most to least units:

  • Mircom BL-10A motor bells (10” gong)
  • Fire-Lite/Notifier MB-G10-24 motor bells (10” gong)
  • Edwards 439D-10AWC vibrating bells (10” gong)
  • Notifier KMS-10-24VDC/P motor bells (10” gong)
  • Mircom BL-6B motor bells (6” gong)
    There is a Mircom “Select-A-Horn/Strobe” FHS-340R horn/strobe (red, wall-mount, set to electromechanical/15cd) in the corridor between this building and Brentview Tower.

Initiating Devices

Pull Stations

Most pull stations are Notifier NFM-950B conventional single-action pull stations.
Some areas have Notifier MPS-950B conventional single-action pull stations as deficiency replacements.
Other areas have Fire-Lite FM-950B conventional single-action pull stations.
Additionally, some areas have Mircom MS-401 conventional single-action pull stations.
All stations have Notifier MMX-101A addressable monitor modules attached to them.

Automatic Detection Devices

The hallways on each upper floor have Notifier CPX-551A addressable ionization smoke detectors.
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the first floor and in elevator lobbies on all floors.
The electrical rooms, elevator machine room and garbage rooms on all lower floors have Notifier FDX-551RA addressable 135°F fixed-temperature/rate-of-rise heat detectors.
Some aforementioned rooms have Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All CPX and FDX-series detectors are mounted on Notifier BX501 bases.
All FSP and FST-series detectors are mounted on System Sensor B210LPA bases.
The garbage rooms on all upper floors have System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors, monitored by Notifier FMM-101A addressable monitor modules attached to each detector.
The main mechanical room has an FDD CF-135 conventional 135°F fixed-temperature heat detector, monitored by a Notifier FMM-1A addressable monitor module.

Modules

There are Notifier CMX-2A addressable relay modules serving various purposes.

EOLs

There are Notifier EOL-CR end of line resistor plates on all signal circuits.