Motel 6 Red Deer, AB

From FireAlarmPedia
Revision as of 17:07, 13 October 2024 by TwentyThree33 (talk | contribs) (Android > iPhone)
System Specifications
FACP: Notifier NFS-640C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2006

Motel 6 is a hotel/motel chain owned by G6 Hospitality. They are headquartered in Carrollton, Texas, USA, and have locations across North America. This particular hotel is located at 5001 19 Street, in Red Deer, Alberta, Canada. The hotel was built in 2006, and the fire alarm system is original.

System Specifications

FACP

The building is protected by a Notifier NFS-640C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All common area notification appliances are System Sensor “SpectrAlert” P2415A horn/strobes (red, wall-mount, 15cd).

All guest rooms have System Sensor S2415WA remote strobes (white, wall-mount, 15cd) paired with System Sensor "SpectrAlert Advance" MHWZA silenceable mini-horns (white, wall-mount).

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout all common areas, mounted on Notifier B710LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Notifier FRM-1A addressable relay modules serving various purposes.

There are Notifier ISO-XA isolator modules on the SLC.

EOLs

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.