Revision as of 16:15, 15 October 2024 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST2 <br />FACP Location: Auto Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous? <br>Strobes Synchronized: Yes, per-NAC <br />Date of last known Upgrade: N/A <br />Year Opened: 1999 |} ‘’’Canadian Tire’’’ is a Canadian chain of department/hardware/automotive s...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST2
FACP Location: Auto Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous?
Strobes Synchronized: Yes, per-NAC
Date of last known Upgrade: N/A
Year Opened: 1999

‘’’Canadian Tire’’’ is a Canadian chain of department/hardware/automotive stores. This particular store is located at 388 Country Hills Blvd NE, in Calgary, Alberta, Canada. The store was built in 1999, and the fire alarm system is original.

System Specifications

FACP

The building is protected by an Edwards EST2 addressable fire alarm system. The panel is located in the automotive entrance vestibule. The system runs Edwards’ Signature addressable protocol, and the system coding is likely continuous.

Notification Appliances

All notification appliances are Edwards 439D-10AWC vibrating bells (10” gong) mounted on Edwards 403-5A-R strobe plates (15cd).

Initiating Devices

Pull Stations

All pull stations but one are EST SIGA-270 addressable single-action pull stations.
There is an EST SIGA-278 addressable dual-action pull station at the garden centre exit as a deficiency replacement.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors at the top of each stairwell, mounted on EST SIGA-SB bases.
There are EST SIGA-DH duct smoke detector housings with EST SIGA-PS addressable photoelectric heads on all air handling units.

Modules

There are EST SIGA-WTM addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.

EOLs