New Brighton Child Care

From FireAlarmPedia
Revision as of 20:06, 28 April 2025 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C <br />FACP Location: West Foyer <br />System Type: Two-Stage Addressablae <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: N/A <br />Year Opened: 2014 |} '''New Brighton Child Care''' is a daycare located at 6 New Brighton Heath SE, Calgary, Albert...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS-320C
FACP Location: West Foyer
System Type: Two-Stage Addressablae
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2014

New Brighton Child Care is a daycare located at 6 New Brighton Heath SE, Calgary, Alberta. The centre opened in 2014, and the fire alarm system is original.

System Specifications (2014-present)

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the west foyer. The system runs Notifier's FlashScan addressable protocol, and is configured for two-stage operation. The alert signal is 20BPM, followed by temporal as the alarm signal.

Notification Appliances

All notification appliances are System Sensor "SpectrAlert Advance" P4RA horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors in all corridors, stairwells and some rooms.
There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in the mechanical room, washrooms and kitchen.
All aforementioned detectors but one are mounted on System Sensor B210LPA bases, while the upstairs washroom heat detector is on a System Sensor B224BIA isolator base.
The attic has System Sensor 5604A conventional 190°F fixed-temperature heat detectors, all wired to a single Notifier FMM-1A addressable monitor module.

Modules

There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.

EOLs