System Specifications |
---|
FACP: Notifier NFS-320C
FACP Location: Main Entrance System Coding: Temporal Strobes Synchronized: Yes |
40 Sunpark Plaza SE is a mixed-use 3-story office complex located in the Sundance neighborhood of Calgary, Alberta, Canada. The first floor contains a doctor's office, a Shoppers Drug Mart, and formerly an optometrist. It was built in 2004, and the current fire alarm system was installed in 2020.
System Specifications
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. This system runs Notifier's FlashScan addressable protocol, and the system coding is temporal. The permit issued for the upgrade was "Fire Alarm Repair (Sunpark Professional Building)" on May 28, 2020.
Notification Appliances
Most notification appliances are System Sensor P2RLA horn/strobes (red, wall-mount, bilingual lettering, set to 15cd). Some areas such as washrooms have System Sensor SRLA remote strobes (red, wall-mount, bilingual lettering, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the facility, mounted on System Sensor B210LPA low-profile bases.
System Specifications (original system)
System Specifications |
---|
FACP: Notifier AFP-200 System Type:Addressable System Line Voltage: 120VAC NAC Voltage:24VDC Date of last known Upgrade: late 2010s Year Decomissioned: 2020 |
FACP
The building was protected by a Notifier AFP-200 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Notifier's CLIP addressable protocol, and the system coding was temporal. This panel is now owned by Yycsfirealarmnimrod. and is now in use in YYCsFireAlarmNimrod's Basement. The panel is fully functional, and was replaced due to NAC troubles. However the culprit was found to have been faulty horn/strobe installation.
Notification Appliances
All notification appliances were System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd). These were installed in 2015, and replaced System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd). There was also a Mircom "Select-A-Horn/Strobe" FHS-340R horn/strobe (red, wall-mount, set to 15cd/broadband) in the atrium, which was also replaced in 2013.
Initiating Devices
Pull Stations
All pull stations were Notifier MPS-950B conventional single-action pull stations, All pull stations were wired to Notifier FMM-101A addressable modules, which were located directly behind each station.
Automatic Detection Devices
There were Notifier FSP-851A addressable photoelectric smoke detectors located throughout the building, mounted on System Sensor B210LPA low-profile bases. These may be in use on the current system, however this is unconfirmed.