Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Calgary Fire Department Station 30

From FireAlarmPedia
Revision as of 14:27, 4 August 2024 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Simplex 4007ES <br />FACP Location: Main Entrance Vestibule <br />System Type: Single...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Simplex 4007ES
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2021
Year Opened: 1997

The Calgary Fire Department is the fire department serving The City of Calgary. This page will cover Station 30, located at 6 McKenzie Towne Gate SE, in Calgary, Alberta, Canada. The station was built in 1997, and the fire alarm system was upgraded in 2021.

System Specifications (2021-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

Most indoor notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).
Some areas have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd) for additional visual coverage.
For outdoor notification, there is a Simplex 4906-9105 weatherproof remote strobe (red, wall-mount) outside the main entrance.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9004 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building.
Some areas, such as closets and mechanical rooms, have Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on Simplex 4098-9792 bases.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on the SLC.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.