Westbrook Mall

From FireAlarmPedia
Revision as of 14:28, 4 August 2024 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST3 <br />FACP Location: TBA <br />System Type: Two-Stage Addressable <br />...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: TBA
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (alert)
Temporal (alarm)
Strobes Synchronized: Yes, EST
Date of last known Upgrade: 2002
Year Opened: 1964

Westbrook Mall is a shopping mall located at 1200 37 Street NW, Calgary, Alberta. The anchor tenants are Safeway and Walmart. The mall opened in 1964, and underwent renovations in 2002. The fire alarm system was upgraded during the renovation.

System Specifications (2002-present)

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located… The system runs Edwards’ Signature addressable protocol, and is configured for two-stage operation. Alert signal coding is 20BPM, followed by temporal for the alarm signal.

Notification Appliances

Most notification appliances are Edwards “Integrity” 757-5A-T horn/strobes (red, wall-mount, set to 15cd), mounted on the ceiling.
Walmart has Edwards 757-1A-TW remote horns (white wall-mount) on poles opposite of each other, and two EST “Genesis” G1-VM remote strobes (white, wall-mount, no marking, set to 15cd) on each side.
There are Edwards G1-HD remote horns (white, wall-mount, no marking) in Walmart as deficiency replacements.

Initiating Devices

Pull Stations

Most pull stations are EST SIGA-270P addressable two-stage pull stations.
Walmart and Safeway have EST SIGA-270 addressable single-stage single-action pull stations for unknown reasons.
There is one Edwards 270-SPO conventional single-action pull station in the mall entrance to Safeway, wired to an EST SIGA-CT1 addressable monitor module.

Automatic Detection Devices

None noticed. The mall has a sprinkler system.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs

There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.