Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Scenic Bow Group Home 19

From FireAlarmPedia
Revision as of 14:28, 4 August 2024 by Alberta Fire Alarms (talk | contribs) (Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Simplex 4007ES <br />FACP Location: Staff Office <br />System Type: Two-Stage Hybrid-...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Simplex 4007ES
FACP Location: Staff Office
System Type: Two-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: N/A
Date of last known Upgrade: 2023
Year Opened: 1987

Scenic Bow Place is an assisted living facility operated by Alberta Health Services. This page will cover Group Home 19, located at #108 100 Scenic Bow Place NW, in Calgary, Alberta, Canada. The home was built in 1987, and the fire alarm system was upgraded in 2023.

System Specifications (2023-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4007ES hybrid-addressable fire alarm system. The panel is located in the staff office. The system runs Simplex’s IDNet addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the alarm coding is temporal. The timer length is three minutes.

Notification Appliances[edit | edit source]

All notification appliances are Simplex “TrueAlert” 49CMT-WRF remote horns (red, wall-mount, set to tone).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building.
The main living area and corridor have System Sensor C2W-BA conventional photoelectric smoke detectors.
Smaller rooms have Simplex 4098-9734 addressable 190°F fixed-temperature/rate-of-rise heat detectors.
All aforementioned addressable detectors are mounted on Simplex 4098-9792 bases.
There are Simplex 4098-9755 addressable photoelectric duct smoke detectors on all fan units.
There is a Simplex 4098-XAD-110 addressable aspirating smoke detector supervising the padded room.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising all dampers and fan units.
There are Simplex 4090-9002 addressable relay modules for HVAC control.
There are Simplex 4090-9116 addressable isolator modules on the SLC.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all conventional circuits.