System Specifications
FACP: EST iO500
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2014

292136 Crossiron Drive is the address of a small industrial plaza in Rocky View, Alberta, Canada. The building opened in 2014, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main electrical room. The system runs EST’s Signature addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

Most notification appliances are Edwards “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). The warehouses have Edwards GCF-HDVM horn/strobes (white, ceiling-mount, FIRE Lettering, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are no detectors installed in this building. The building is equipped with a wet sprinkler system.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the fire pump, sprinkler tamper and flow switches.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all generator, sprinkler and signal circuits.