System Specifications
FACP: Fire-Lite ES-200X
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2023

700 80 Longview Common SE is the address of a small retail plaza in the Township shopping district of Calgary, Alberta, Canada. The plaza consists of Toys ‘R’ Us and Shoppers Drug Mart. The plaza was built in 2023, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Fire-Lite ES-200X addressable fire alarm system. The panel is located in the main electrical room at the rear of the building. The system runs Fire-Lite’s LiteSpeed addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There are Fire-LIte ANN-LED annunciators in the main entrance vestibule of each store.

Notification Appliances[edit | edit source]

All indoor notification appliances are System Sensor “L-Series” PC2WLA horn/strobes (white, ceiling-mount, set to 15cd).
For outdoor notification, there is a System Sensor “SpectrAlert Advance” SRKA weatherproof remote strobe (red, wall-mount) outside the main electrical room.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Fire-Lite BG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed.

Modules[edit | edit source]

There are Fire-Lite MMF-300A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Fire-Lite I300A isolator modules on the SLC.

EOLs[edit | edit source]

There are Fire-Lite EOL-CR end of line resistor plates on all sprinkler and signal circuits.