6106-6112 8650 112 Ave NW, Calgary

From FireAlarmPedia
Revision as of 09:54, 7 September 2024 by TwentyThree33 (talk | contribs) (TwentyThree33 moved page 6106-6112 8650 112 Ave NW to 6106-6112 8650 112 Ave NW, Calgary without leaving a redirect: Page was made prior to Fire Alarmpedia expanding beyond Calgary. Move is being done to avoid confusion with other cities.)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SS
Date of last known Upgrade: N/A
Year Opened: 2012

Royal Oak Park Shopping Centre is a shopping centre located at 8650 112 Ave NW. It consists of multiple buildings. This page will cover the 6000 building, which is a small commercial plaza, with unit numbers 6106-6112. It consists of A-Mart and Jerusalem Shawarma. It was built in 2012, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Notifier ACM-24AT LED annunciator in the A-Mart entrance vestibule.

Notification Appliances[edit | edit source]

All indoor notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount, set to 75cd) outside the electrical room.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.