Beltline Aquatic & Fitness Centre

From FireAlarmPedia
Revision as of 14:17, 8 September 2024 by TwentyThree33 (talk | contribs)
System Specifications
FACP: Mircom FX-2000
FACP Location: Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, SS
Date of last known Upgrade: 2024
Year Opened: 1954

Beltline Aquatic & Fitness Centre (also known as Beltline Community Hub prior to closure) is a closed recreation facility located at 223 12 Ave SW. It featured an indoor swimming pool, gymnasium, weight room and a climbing wall, etc. The facility opened in 1954, and the fire alarm system was upgraded in 2014. The facility has been closed since October 2022, but had a panel upgrade recently.

System Specifications (2014-present)

FACP

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance. The system runs Mircom’s Advanced addressable protocol, and the system coding is temporal.
This FX-2000 was installed in 2024, as an emergency replacement for the variant installed during the 2014 upgrade.

Notification Appliances

Most notification appliances are from System Sensor’s “SpectrAlert Advance” line of products.
Most notification appliances are System Sensor PC2WA horn/strobes (white, ceiling-mount, set to 15cd).
The pool area and mechanical rooms have System Sensor P2RA-B horn/strobes (red, wall-mount, bilingual lettering, set to 15cd)
There is a System Sensor “L-Series” PC2WLA horn/strobe (white, ceiling-mount, set to 15cd) in the mens’ locker room as a deficiency replacement.

Initiating Devices

Pull Stations

All pull stations are Mircom MS-401AP addressable single-action pull stations.

Automatic Detection Devices

There are Mircom MIX-5251RAPA addressable fixed-temperature/rate-of-rise heat detectors throughout the building.
The top of each stairwell has a Mircom MIX-2251APA addressable photoelectric smoke detector.
All detectors are mounted on System Sensor B210LPA bases.

Modules

There is a System Sensor MDL3WA synchronization module on the NAC to sync all horns and strobes.

EOLs

There are Mircom MP-300 end of line resistor plates on all signal circuits.