System Specifications
FACP: Notifier NFS-320C
FACP Location: Admin. Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2020
Year Opened: 1995

The Calgary Food Bank is a non-profit organization located at 5000 11 Street SE, in Calgary, Alberta, Canada. The building was built in 1995, and the fire alarm system was upgraded in 2020.

System Specifications (2020-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the administrative entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Power Supplies[edit | edit source]

There is a Notifier FCPS-24S6C booster power supply at the main entrance.

Notification Appliances[edit | edit source]

Most notification appliances are System Sensor "L-Series" P2RLA horn/strobes (red, wall-mount, set to 15cd).

The office area washrooms have System Sensor SRLA remote strobes (red, wall-mount, set to 15cd).

The public washrooms have System Sensor SGRLA low-profile remote strobes (red, wall-mount, set to 15cd).

The freezers have System Sensor “SpectrAlert Advance” P2RKA weatherproof horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There is a Notifier FSP-851A addressable photoelectric smoke detector at the top of the former stairs, mounted on a System Sensor B210LPA low-profile base.
There are several System Sensor DNRA duct smoke detectors, with Notifier FSP-851A heads.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

There are Notifier FRM-1A addressable relay modules controlling the door magnets,

There are Notifier ISO-6A isolator cards in a cabinet by the main FACP.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.