ICE District Connect Centre

From FireAlarmPedia
Revision as of 11:30, 30 September 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards EST3
FACP Location: Unknown
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: Unknown
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2022

The ICE District Connect Centre is an entertainment/retail plaza located adjacent to Rogers Place, at 10324 103 Street NW, in Downtown Edmonton, Alberta, Canada. The plaza’s primary tenants are Loblaws City Market, Plantlife, ICE District Authentics, and The Canadian Icehouse. The building was built in 2022, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST3 addressable fire alarm system. This is likely a networked system; the panel locations are unknown. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the messages and/or tones are unknown at this time.

Notification Appliances[edit | edit source]

Common Areas & Most Units[edit | edit source]

Most notification appliances are Edwards “Genesis” GCF-S7VM speaker/strobes (white, ceiling-mount, FIRE marking, 70V, set to 15cd).
Some areas have Edwards G4F-S7VM speaker/strobes (white, wall-mount, FIRE marking, 70V, set to 15cd).
Plantlife has an Edwards GCSVWN speaker/strobe (white, ceiling-mount, no marking, set to 70V/15cd).
For outdoor notification, there is an Edwards “Integrity” 757-1A-SS70W remote speaker (white, wall-mount, 70V) paired with an Edwards CS405-7A-T weatherproof remote strobe (red, wall-mount, 15/75cd).

ICE District Authentics[edit | edit source]

This unit has a mix of Edwards “Genesis” G4SVWF speaker/strobes (white, wall-mount, FIRE marking, set to 70V/15cd) and Edwards GCSVWF speaker/strobes (white, ceiling-mount, FIRE marking, set to 70V/15cd).

Pedway[edit | edit source]

All areas of the pedway have Edwards “Genesis” GCSVWF speaker/strobes (white, ceiling-mount, FIRE marking, set to 70V/15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Edwards SIGA-OSD addressable optical smoke detectors in most areas, mounted on Edwards SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all signal and sprinkler circuits.