Joane Cardinal Schubert High School

From FireAlarmPedia
Revision as of 13:27, 30 September 2024 by TwentyThree33 (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Edwards iO1000
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: N/A
Year Opened: 2018

Joane Cardinal Schubert High School is a high school located at 19480 45 Street Southeast, in Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education. The school serves many neighborhoods, including Seton, Copperfield, Mahogany and New Brighton. The school opened in 2018, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards iO1000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All areas except washrooms have Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). The student washrooms have Edwards G1R-VM remote strobes (red, wall-mount, no lettering, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Edwards SIGA-PD addressable photoelectric smoke detectors throughout the school, mounted on Edwards SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are EST SIGA-CR addressable relay modules serving various purposes.

There are EST SIGA-IM addressable isolator modules on all SLCs.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.