RONA+ (MacLeod)

From FireAlarmPedia
Revision as of 22:49, 9 October 2024 by Alberta Fire Alarms (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
System Specifications
FACP: Simplex 4010

FACP Location: Next to Customer Service
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC

System Coding: Temporal?

Strobes Synchronized: No
Date of last known Upgrade: 2004
Year Opened: 1994

RONA+ is a hardware store chain. This particular location is located at 9630 MacLeod Trail SE, Calgary, Alberta, Canada. It was built in 1994 as a Revy, became RONA in 2004, and was converted to a Lowe's in 2018. The fire alarm system was unaffected by these changes, however only some notification appliances are original.

System Specifications (2004-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4010 addressable fire alarm system. The panel is located just past the main entrance, adjacent to the customer service desk. It was installed in the 2000s replacing the original EST ESA2000; the cabinet remains. The system runs Simplex's IDNet addressable protocol, and the system coding is likely temporal.

Notification Appliances[edit | edit source]

The notification appliances consist of the original Edwards 439D-10AWC vibrating bells and Edwards 802-2B remote strobes. Replacement notification appliances are Simplex 2901-9724 motor bells and Simplex "TrueAlert" 4906-9101 (red, wall) remote strobes.

Most of the notification appliances are the original Edwards 439D-10AWC vibrating bells (10" gong) and Edwards 802-2B remote strobes (red, wall-mount, 0.47cd). Deficiency replacments include: Simplex 2901-9724 motor bells (10" gong), Simplex "TrueAlert" 4906-9101 remote strobes (red, wall-mount, set to 15cd), and an Edwards 202-5A-T (red, wall-mount, 15cd) near the front.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All of the pull stations are Simplex 4099-9001 addressable, single action T bar pull stations.

Automatic Detection Devices[edit | edit source]

None noticed.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler and signal circuits.